Teck90 600V, 50+G C #14+14 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 50+G Conductor 14+14AWG (7x22H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

6064 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
6064 0102500Reel612825339229Order online
6064 010984Reel—Order online

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Overall Cable Diameter (Nominal)1.642 in (41.71 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)5014 AWG7x22BC - Bare Copper
Ground Wire114 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.132 in (3.35 mm)Black and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.276 in (32.41 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.034 in (0.86 mm)
Diameter Over Armor1.536 in (39.01 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.053 in (1.3 mm)
Nom. Diameter1.642 in (41.71 mm)

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)2.65 Ohm/1000ft12.5 Amps per Conductor at 30oC
Ground Wire2.67 Ohm/1000ft (8.76 Ohm/km)25 Amps per Conductor at 30oC

Voltage

Voltage Rating600 V (TECK 90)

Mechanical Characteristics

Max. Pull Tension2984.6 lbs (1353.8 kg)
Bulk Cable Weight1471 lbs/1000ft

Temperature

UL Temperature90°C
Operating-40°C To +90°C

Bend Radius

Stationary Min.13.136 in (333.65 mm)
Installation Min.13.136 in (333.65 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceTECK 90, HL.

History

Update and RevisionRevision Number: 0.63 Revision Date: 05-31-2024