Belden Store
6059

Product Number: 6059

Teck90 600V, 3+3+G C #8+14+10 Str BC, XLPE Ins, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 3+3+G Conductor 8+14+10AWG (7x16H+7x22H) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

6059 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Put-Up TypeUPCOrder
6059 0104920Reel612825339151Order online
6059 0101968Reel—Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.450 Revision Date: 03-18-2026

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Physical Characteristics (Overall)

Conductor Count6

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor187x16BC - Bare Copper3
Conductor2147x22BC - Bare Copper3
Ground107x18BC - Bare Copper1

Insulation

ElementConductor1
MaterialXLP, XLPO, XLPE (Thermoset)
Nominal Diameter0.133 in
Nominal Wall Thickness0.031 in

Color Chart

NumberColor
1Black
14Black
2Red
14Red
3Blue (14 AWG); Black
14Blue
1Red
8Black
2Blue (8 AWG)
8Red
3
8Blue

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.7 in

Outer Jacket

MaterialNominal DiameterNominal Wall Thickness
PVC - Polyvinyl Chloride1.024 in0.048 in
0.981 in

Construction and Dimensions

Armor

Type of ArmorInterlocked
MaterialAluminum

Electrical Characteristics

Conductor DCR

ElementNominal Conductor DCR
14 AWG0.667 Ohm/1000ft
10 AWG2.67 Ohm/1000ft

Current

Max. Recommended Current [A]
55 Amps per Conductor at 30oC
25 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V

Temperature Range

UL Temperature Rating90°C
Operating Temperature Range-40°C To +90°C
Wet Temp Range-40°C To +90 °C
Dry Temp Range-40°C To +90 °C

Mechanical Characteristics

Bulk Cable Weight567 lbs/1000ft
Maximum Recommended Pulling Tension570 lbs
Minimum Bend Radius During Installation8.192 in
Minimum Minor Axis Bend Radius9.8 in

Standards

CSA AWM ComplianceCSA C22.2#131; Hazardous Locations CSA C22.2#0.3 Clause 4.31 Low Acid Gas

Applicable Environmental and Other Programs

EU Directive ComplianceEU Directive 2003/11/EC (BFR)
MII Order #39 (China RoHS)Yes

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

CSA/C(UL) FlammabilityFT4
UL FlammabilityUL1685 UL Loading

Plenum/Non-Plenum

Plenum (Y/N)No

History

Update and RevisionRevision Number: 0.450 Revision Date: 03-18-2026

Resources

Related control cable