Belden Store
6052

Product Number: 6052

Teck90 600V, 20+G C #14+14 Str BC, XLPE Ins M4, PVC Jkt, SIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 20+G Conductor 14+14AWG (7x22H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Steel Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Overall Cable Diameter (Nominal)1.237 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)2014 AWG7x22BC - Bare Copper
Ground Wire114 AWG7x22BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.132 in (3.35 mm)Black and Numbered
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.085 in (2.2 mm)
Nom. Diameter0.885 in (22.5 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialSIA - Steel Interlock Armor
Armor Thickness0.034 in (0.86 mm)
Diameter Over Armor1.141 in (28.98 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter1.237 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)2.65 Ohm/1000ft17.5 Amps per Conductor at 30oC
Ground Wire2.67 Ohm/1000ft (8.76 Ohm/km)

Voltage

Voltage Rating600 V (TECK 90)

Mechanical Characteristics

Max. Pull Tension1346.6 lbs (610.81 kg)
Bulk Cable Weight1097 lbs/1000ft

Temperature

UL Temperature90°C
Operating-40°C To +90°C

Bend Radius

Stationary Min.9.896 in (251.4 mm)
Installation Min.9.896 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
CEC / C(UL) ComplianceTECK 90, HL.

History

Update and RevisionRevision Number: 0.55 Revision Date: 03-18-2026

Resources

Related control cable