Belden Store
6051

Product Number: 6051

Teck90 600V, 3+3+G C #10+14+12 Str BC, XLPE Ins, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 3+3+G Conductor 10+14+12AWG (7x18H+7x22H) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

6051 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
6051 0105000Reel612825338932Order online
6051 0102500Reel—Order online

Specifications

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Construction Details

Overall Cable Diameter (Nominal)0.897 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor1310 AWG7x18BC - Bare Copper
Conductor2314 AWG7x22BC - Bare Copper
Ground Wire112 AWG7x20BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor1XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.174 in (4.42 mm)Black, Blue, Red
Conductor2XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.132 in (3.35 mm)Black, Red, Blue
Ground WireNo Insulation

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.576 in (14.6 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.025 in (0.64 mm)
Diameter Over Armor0.801 in (20.3 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter0.897 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor12.5 Ohm/1000ft32 Amps per Conductor at 30oC
Conductor21.1 Ohm/1000ft (3.6 Ohm/km)

Voltage

Voltage Rating600 V (TECK 90)

Mechanical Characteristics

Max. Pull Tension794.2 lbs (360.2 kg)
Bulk Cable Weight425 lbs/1000ft

Temperature

UL Temperature90°C
Operating-40°C To +90°C
Installation-25°C To +90°C

Bend Radius

Stationary Min.7.176 in (182.3 mm)
Installation Min.7.176 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, UV Resistance
AWM ComplianceC22.2 #131; Hazardous Location; C22.2 #0.3 Clause 4.31 Low Acid Gas
CEC / C(UL) ComplianceTECK 90, HL.

History

Update and RevisionRevision Number: 0.175 Revision Date: 03-18-2026