Belden Store
6049

Product Number: 6049

Teck90 600V, 50+G C #12+14 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C

Teck90 600V, 50+G Conductor 12+14AWG (7x22H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.80 Revision Date: 03-26-2026

Product Overview

Suitable ApplicationsCEC Power and Control Applications

Physical Characteristics (Overall)

Conductor Count50

Conductor

ElementAWGStrandingMaterialNo. of Conductors
Conductor(s)127x20.5BC - Bare Copper50
Ground147x22BC - Bare Copper1
Ground7x20BC - Bare Copper

Insulation

ElementMaterialNominal DiameterNominal Wall Thickness
Conductor1XLP, XLPO, XLPE (Thermoset)0.174 in0.030 in
Ground WireNo Insulation

Color Chart

ColorBlack and Numbered

Inner Jacket

MaterialPVC - Polyvinyl Chloride
ColorBlack
RipcordYes

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Wall Thickness0.053 in

Construction and Dimensions

Armor

Type of ArmorInterlocked
MaterialAluminum

Electrical Characteristics

Current

Max. Recommended Current [A]21 Amps per Conductor at 30oC

Voltage

Non-UL DescriptionTECK 90

Temperature Range

Operating Temperature Range-40°C To +90°C
Dry Temp Range-40°C To +90 °C

Mechanical Characteristics

Bulk Cable Weight1957 lbs/1000ft

Standards

CSA AWM ComplianceCSA C22.2#131; Hazardous Locations CSA C22.2#0.3 Clause 4.31 Low Acid Gas

Applicable Environmental and Other Programs

EU Directive ComplianceEU Directive 2003/11/EC (BFR)

Suitability

Suitability - IndoorYes
Suitability - OutdoorYes
Suitability - Sunlight ResistanceYes

Flammability, LS0H, Toxicity Testing

CSA/C(UL) FlammabilityFT4

History

Update and RevisionRevision Number: 0.80 Revision Date: 03-26-2026