Belden Store
29008

Product Number: 29008

ACIC 600V, 30+G C #16 Str BC, XLPE Ins, PVC Jkt, AIA Armor, PVC Jkt, 90C Dry/Wet SUN RES -40C

Canadian Instrumentation Cable TC-ACIC 600V, 30+G Conductor 16AWG (7x24) Bare Copper, XLPE Insulation, PVC Inner Jacket, Aluminum Interlock Armor, PVC Outer Jacket, 90C Dry/Wet SUN RES -40C

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

29008 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeOrder
29008 J225002ReelOrder online

Specifications

Product Overview

Suitable ApplicationsPower and Control Applications up to 600V

Construction Details

Armor Table NotesSeprator -Corrugated Mylar Tape
Overall Cable Diameter (Nominal)1.325 in

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)3016 AWG7x24BC - Bare Copper
Ground Wire116 AWG7x24BC - Bare Copper

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)White and Numbered, Black and Numbered
Ground WireXLP, XLPO, XLPE (Thermoset)0.030 in (0.76 mm)0.118 in (3.00 mm)Green

Outer Shield

MaterialNo Shield

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter0.961 in (24.4 mm)
RipcordYes
ColorBlack

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor
Armor Thickness0.034 in (0.86 mm)
Diameter Over Armor1.221 in (31.01 mm)

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.052 in (1.3 mm)
Nom. Diameter1.325 in

Electrical Characteristics

Electricals

ElementNom. Conductor DCRMax. Current
Conductor(s)4.2 Ohm/1000ft10.8 Amps per Conductor at 30oC
Ground Wire4.2 Ohm/1000ft (14 Ohm/km)10 Amps per Conductor at 25oC

Voltage

Voltage Rating600 V

Mechanical Characteristics

Max. Pull Tension1307 lbs (592.8 kg)
Bulk Cable Weight846 lbs/1000ft

Temperature

Operating-40°C To +90°C

Bend Radius

Stationary Min.15.9 in (404 mm)
Installation Min.15.9 in

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
CEC / C(UL) ComplianceHL, ACIC.
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.315 Revision Date: 12-22-2023

Resources