Belden Store
FM4MFB1100MLMNE

Product Number: FM4MFB1100MLMNE

FMT OM4 MPO12(F-F) B 12F 100M ZH/OFNR MD_4.8 0.5xIL NxPE EV

FX MPO TRUNK, OM4, MPO-12(FEMALE TO FEMALE), TYPE-B, 1 MPO (12 FIBERS), 100 M, LSZH/OFNR, MINI-DISTRIBUTION 4.8 MM (DOUBLE JACKET), FAN-OUT: 0.5M x IN-LINE, NO PULLING EYE, ERIKA VIOLET JACKET

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsData Center, LAN, Equipment Room, Telecommunication room, Workstation Area

Fiber Specifications

Fiber Core Diameter50/125 μm
Fiber Count12
Fiber Color CodeTIA-598-D

Physical Specifications

Connectors

DescriptionTypeHousing MaterialHousing ColorBoot MaterialBoot Color
Connector A (Inside End)MPO-12 FemalePlasticErika VioletRubberBlack
Connector B (Outside End)MPO-12 FemalePlasticErika VioletRubberBlack

Fan-out (Legs)

DescriptionTransitionLength (m)DiameterGeometry
Connector A (Inside End)LPM0.5 m3.0 mmIn-Line
Connector B (Outside End)LPM0.5 m3.0 mmIn-Line

Assembly Cable

Cable Nominal OD4.8 mm
Jacket ColorErika Violet

Measurement

Overall Assembly Length100 m (328 ft)
PackagingIndividually packaged in a plastic spool

Overall Length Tolerances

RangeTolerance
0 to 2 meters+0.2 / -0 meter
2.1 to 4.9 meters+0.3 / -0 meter
5 to 40 meters+0.4 / -0 meter
over 40 meters+1.0% / -0%

Armor Specifications

Armor Type and MaterialNo Armor

Optical Characteristics

Polarity IdentificationType-B

Fiber Connector Performance

DescriptionConnector TypeMax. Insertion LossMin. Return Loss
Connector A (Inside End)MPO-12 Female0.20 dB-25 dB
Connector B (Outside End)MPO-12 Female0.20 dB-25 dB

Mechanical Characteristics

Pulling Eye TypeNo Pulling Eye
Minimum Bend Radius During Installation15x Cable OD
Minimum Bend Radius During Operation10x Cable OD

Temperature Range

Operating Temperature Range-10°C To +60°C
Storage Temperature Range-10°C To +60°C

Standards and Compliance

Environmental SuitabilityIndoor
Flammability / Reaction to FireLSZH
UL RatingLow Smoke
TIA/EIA ComplianceTIA/EIA 568.3
European Directive ComplianceEU Directive 2011/65/EU (RoHS 2)
MII Order #39 (China RoHS)EUP 50
Other Standard Compliance(s)ACMA

Product Notes

Related PartsDCX system, FX UHD Patch Panels, ECX Patch Panels, FX Patch cords, FX MPO Trunks, FX Multi-fiber Trunks