FXPC OS2 6_LC_DX MPO12_F xxxM OFNP RD_3.0 TYPE-A YL_JKT
FX PATCH CORD, OS2, 6 x LC DUPLEX - MPO-12 (F), xxx M (LENGTH IN METERS), OFNP, ROUND 3.0 MM, TYPE-A, YELLOW JACKET
- Availability
- Global
- Status
- Active
Specifications
Product Overview
| Suitable Applications | Data Center, LAN, Equipment Room, Telecommunication room, Workstation Area |
|---|
Fiber Specifications
| Fiber Type | OS2 |
|---|---|
| Fiber Core Diameter | 9/125 μm |
| Fiber Count | 12 |
| Fiber Color Code | TIA-598-D |
Physical Specifications
Connectors
| Description | Type | Housing Material | Housing Color | Ferrule | Boot Material | Boot Color |
|---|---|---|---|---|---|---|
| Connector A (Inside End) | LC Duplex | Plastic | Blue | Zirconia Ceramic | Rubber | Blue |
| Connector B (Outside End) | MPO-12 Female | Plastic | Green | Rubber | Black |
Fan-out (Legs)
| Description | Connector A (Inside End) |
|---|---|
| Transition | LPM |
| Length (m) | 0.5 m |
| Diameter | 2.0 mm |
| Geometry | In-Line |
Assembly Cable
| Cable Nominal OD | 3.0 mm |
|---|---|
| Jacket Color | Yellow |
Measurement
| Overall Assembly Length | xxx meters |
|---|---|
| Packaging | Individually packaged in a plastic bag |
Overall Length Tolerances
| Range | Tolerance |
|---|---|
| 0 to 2 meters | +0.2 / -0 meter |
| 2.1 to 4.9 meters | +0.3 / -0 meter |
| 5 to 40 meters | +0.4 / -0 meter |
| over 40 meters | +1.0% / -0% |
Armor Specifications
| Armor Type and Material | No Armor |
|---|
Optical Characteristics
| Polarity Identification | Type-A |
|---|
Fiber Connector Performance
| Description | Connector Type | Max. Insertion Loss | Min. Return Loss |
|---|---|---|---|
| Connector A (Inside End) | LC Duplex | 0.25 dB | 55 dB |
| Connector B (Outside End) | MPO-12 Female | 0.35 dB | 60 dB |
Mechanical Characteristics
| Minimum Bend Radius During Installation | 15x Cable OD |
|---|---|
| Minimum Bend Radius During Operation | 10x Cable OD |
Temperature Range
| Operating Temperature Range | -10°C To +60°C |
|---|---|
| Storage Temperature Range | -10°C To +60°C |
Standards and Compliance
| Environmental Suitability | Indoor |
|---|---|
| Flammability / Reaction to Fire | OFNP |
| UL Rating | Plenum |
| TIA/EIA Compliance | TIA/EIA 568.3 |
| European Directive Compliance | EU Directive 2011/65/EU (RoHS 2) |
| MII Order #39 (China RoHS) | EUP 50 |
| Other Standard Compliance(s) | ACMA |
Product Notes
| Related Parts | DCX system, FX UHD Patch Panels, ECX Patch Panels, FX Patch cords, FX MPO Trunks, FX Multi-fiber Trunks |
|---|
History
| Update and Revision | Revision Number: 0.19 Revision Date: 10-21-2025 |
|---|