Belden Store
1619AM

Product Number: 1619AM

CATV Video, RG11, 14 AWG BCCS, Quad Shield, Messenger

Series 11, 14 AWG solid .064" bare copper-covered steel conductor, gas-injected foam polyethylene insulation, Duobond® IV quad shield (Foil + 60% Braid + Foil + 40% Braid), PVC jacket.

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

1619AM is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPut-Up TypeLengthUPCOrder
1619AM 0101000BlackReel1,000 ft612825119319Order online

Specifications

Physical Characteristics (Overall)

Conductor Count1
Insulation Table NotesGas Injected

Conductor

AWG14
StrandingSolid
MaterialBCCS - Bare Copper Covered Steel
Nominal Diameter0.064 in
No. of Coax1

Insulation

MaterialPE - Polyethylene (Foam)
Nominal Diameter0.28 in

Outer Shield

TypeLayerMaterialMaterial Trade NameCoverage [%]
Tape1Tri-Laminate (Alum+Poly+Alum)Duofoil®100%
Braid2Aluminum60%
Tape3Tri-Laminate (Alum+Poly+Alum)Duofoil®100%
Braid4Aluminum40%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nominal Diameter0.407 x 0.56 in

Construction and Dimensions

OuterJacket1, Messenger Diameter0.072 in
OuterJacket1, Messenger MaterialGalvanized Steel

Electrical Characteristics

Conductor DCR

Nominal Conductor DCR11 Ohm/1000ft
Nominal Outer Shield DCR3 Ohm/1000ft
Outer Conductor DCR3 Ohm/1000ft

Capacitance

Nom. Capacitance Conductor to Shield16.2 pF/ft

Inductance

Nominal Inductance0.097 μH/ft

Impedance

Nominal Characteristic Impedance75 Ohm

Return Loss

Frequency [MHz]5 - 1000 MHz
Min. Structural Return Loss (SRL)20 dB

Delay

Nominal Delay1.2 ns/ft
Nominal Velocity of Propagation (VP) [%]83%

High Frequency

Frequency [MHz]Max. Insertion Loss (Attenuation)
5 MHz0.38 dB/100ft
55 MHz0.96 dB/100ft
211 MHz1.9 dB/100ft
270 MHz2.13 dB/100ft
300 MHz2.25 dB/100ft
350 MHz2.42 dB/100ft
400 MHz2.6 dB/100ft
450 MHz2.75 dB/100ft
550 MHz3.04 dB/100ft
750 MHz3.65 dB/100ft
870 MHz4.06 dB/100ft
1000 MHz4.35 dB/100ft

Voltage

Non-UL Voltage Rating300 V RMS

Temperature Range

Operating Temperature Range-40°C To +80°C

Mechanical Characteristics

Bulk Cable Weight77 lbs/1000ft
Maximum Recommended Pulling Tension220 lbs
Minimum Minor Axis Bend Radius4.5 in

Standards

RG Type11
Series Type11

Applicable Environmental and Other Programs

Environmental SpaceOutdoor - Aerial
EU Directive 2000/53/EC (ELV)Yes
EU Directive 2003/96/EC (BFR)Yes
EU Directive 2011/65/EU (RoHS 2)Yes
EU Directive 2012/19/EU (WEEE)Yes
EU Directive 2015/863/EU (RoHS 2 amendment)Yes
EU Directive ComplianceEU Directive 2003/11/EC (BFR)
EU CE MarkNo
MII Order #39 (China RoHS)Yes

Suitability

Suitability - IndoorYes

Plenum/Non-Plenum

Plenum (Y/N)No

History

Update and RevisionRevision Number: 0.384 Revision Date: 02-20-2026

Resources