Belden Store
29732C

Product Number: 29732C

VFD, 3C #4/0 Str BC XLPE Ins + #3 Symm. Seg. Gnd (3 of #8) Str BC, CTS, Blk PVC Jkt, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B

Belden Basics VFD, 3 Conductor 4/0AWG (19x10) Bare Copper XLPE Insulation M4 Color Code + 3AWG Symmetrical Segmented Ground (3 of 8AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN RES DIR BUR Oil Resistant

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

29732C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
29732C 0101000Reel612825445517Order online
29732C 0101500Reel612825445555Order online
29732C 0102000Reel612825445562Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.312 Revision Date: 04-01-2026

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements

Construction Details

Overall Cable Diameter (Nominal)1.759 in (44.68 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)34/0 AWG19x10BC - Bare CopperASTM B3 Copper B8 Class B Stranding
Ground38 AWG7x16BC - Bare CopperSegmented Grounds

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.093 in (2.4 mm)0.698 in (17.7 mm)Black and Numbered
GroundNo Insulation

Outer Shield

Shield TypeMaterialCoverage
Helical TapeBare Copper (BC)100%
Helical TapeBare Copper (BC)100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.120 in (3.05 mm)
Nom. Diameter1.759 in (44.68 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR0.052 Ohm/1000ft (0.17 Ohm/km)
Nom. Capacitance Cond-to-Cond26 pF/ft (85 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)47 pF/ft (150 pF/m)
Nom. Characteristic Impedence71 Ohm
Nom. Inductance0.136 μH/ft (0.446 μH/m)
Nom. Velocity of Prop.55%
Max. Current260 Amps per Conductor at 30oC

Voltage

UL Voltage Rating2000 V (TC), 1000 V (CSA AWM I/II A/B)

Mechanical Characteristics

Max. Pull Tension7814 lbs (3544 kg)
Bulk Cable Weight2806 lbs/1000ft (4176 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C

Bend Radius

Stationary Min.21.1 in (536 mm)
Installation Min.21.1 in (536 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL ComplianceArticle 336, TC-ER, RHW-2
AWM ComplianceI/II A/B
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)P-07-KA070003-MSHA

History

Update and RevisionRevision Number: 0.312 Revision Date: 04-01-2026

Resources

Related vfd cable