Belden Store
29724C

Product Number: 29724C

VFD, 3C #8 Str BC XLPE Ins + #10 Symm. Seg. Gnd (3 of #14) Str BC, CTS, Blk PVC Jkt, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B

Belden Basics VFD, 3 Conductor 8AWG (7x16) Bare Copper XLPE Insulation M4 Color Code + 10AWG Symmetrical Segmented Ground (3 of 14AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN RES DIR BUR Oil Resistant

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

29724C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #Putup TypeUPCOrder
29724C 0102500Reel612825445494Order online
29724C 0105000Reel612825445500Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.153 Revision Date: 04-01-2026

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements

Construction Details

Overall Cable Diameter (Nominal)0.794 in (20.2 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)38 AWG7x16BC - Bare CopperASTM B3 Copper B8 Class B Stranding
Ground314 AWG7x22BC - Bare CopperSegmented Grounds

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.072 in (1.8 mm)0.286 in (7.26 mm)Black and Numbered
GroundNo Insulation

Outer Shield

Shield TypeMaterialCoverage
Helical TapeBare Copper (BC)100%
Helical TapeBare Copper (BC)100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter0.794 in (20.2 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR0.564 Ohm/1000ft (1.85 Ohm/km)
Nom. Capacitance Cond-to-Cond21 pF/ft (69 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)38 pF/ft (120 pF/m)
Nom. Characteristic Impedence90 Ohm
Nom. Velocity of Prop.55%
Max. Current55 Amps per Conductor at 30oC

Voltage

UL Voltage Rating2000 V (TC), 1000 V (CSA AWM I/II A/B)

Mechanical Characteristics

Max. Pull Tension819 lbs (371 kg)
Bulk Cable Weight444 lbs/1000ft (661 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C

Bend Radius

Stationary Min.9.5 in (240 mm)
Installation Min.9.5 in (240 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU)
NEC / UL ComplianceArticle 336, TC-ER, RHW-2
AWM ComplianceI/II A/B
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)P-07-KA070003-MSHA

History

Update and RevisionRevision Number: 0.153 Revision Date: 04-01-2026

Resources