Belden Store
29556C

Product Number: 29556C

VFD, 3C #2 Str BC XLPE Ins + #5 Symm. Seg. Gnd (3 of #10) Str BC, CTS, Blk PVC Jkt, 1000V CSA TC C22.2 #230 C22.2 #38

Belden Basics CSA VFD, 3 Conductor 2AWG (7x10) Bare Copper XLPE Insulation M4 Color Code + 5AWG Symmetrical Segmented Ground (3 of 10AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 1000V CSA TC C22.2 #230 C22.2 #38 SUN RES DIR BUR Oil Resistance

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; Specific ratings for applications in Canada

Construction Details

Overall Cable Diameter (Nominal)1.090 in (27.69 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)32 AWG7x10BC - Bare Copper
Ground310 AWG7x18BC - Bare CopperSegmented Grounds

Insulation

ElementMaterialNom. ThicknessColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.062 in (1.6 mm)Black and Numbered
GroundNo Insulation

Outer Shield

Shield TypeMaterialCoverage
Helical TapeBare Copper (BC)100%
Helical TapeBare Copper (BC)100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.093 in (2.4 mm)
Nom. Diameter1.090 in (27.69 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR0.14 Ohm/1000ft (0.46 Ohm/km)
Nom. Capacitance Cond-to-Cond50 pF/ft (160 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)90 pF/ft (300 pF/m)
Nom. Characteristic Impedence36 Ohm
Nom. Velocity of Prop.55%
Max. Current130 Amps per Conductor at 30oC

Voltage

UL Voltage Rating1000 V (CSA TC)

Mechanical Characteristics

Max. Pull Tension3027 lbs (1373 kg)
Bulk Cable Weight1048 lbs/1000ft (1560 kg/km)

Temperature

Operating-40°C To 90°C

Bend Radius

Stationary Min.13.1 in (333 mm)
Installation Min.13.1 in (333 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to Fire1202, 383 Vertical Tray Flame Test (70,000 BTU)
CEC / C(UL) ComplianceTC, RW90, C22.2 #230, #38.
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.535 Revision Date: 03-31-2026

Resources

Related vfd cable