Belden Store
29532

Product Number: 29532

VFD 100% Gnd, 3C #4/0 Str TC XLPE Ins + #4/0 Symm. Seg. Gnd (3 of #2) Str BC, CTS, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC

Belden 100% Ground Flexible VFD, 3 Conductor 4/0AWG (7x19x18) Tinned Copper XLPE Insulation M4 Color Code + 4/0AWG Symmetrical Segmented Ground (3 of 2AWG) Bare Copper Stranded in Continuous Contact with Overall Dual Copper Tape Helically Applied Shield, Black PVC Outer Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC 1000V CSA AWM I/II A/B 600V RW90 TC SUN RES DIR BUR Oil Resistant

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

29532 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
29532 0101500BlackReel1,500 m612825332305C ZOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.733 Revision Date: 06-30-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland BTC200A1741RA

Construction Details

Overall Cable Diameter (Nominal)1.620 in (41.15 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)34/0 AWG7x19x18TC - Tinned CopperFine Strand Optomized for VF Applications
Segmented Ground Wire32 AWG7x19x23BC - Bare CopperSegmented Grounds (3 Totaling 4/0 AWG)

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.057 in (1.4 mm)0.669 in (17.0 mm)ICEA Chart M4
Ground WireNo Insulation

Outer Shield

Shield TypeMaterialCoverageNotes
Helical TapeBare Copper (BC)100%2 mil helical copper for crack resistance and high frequency performance
Helical TapeBare Copper (BC)100%2 mil helical copper for crack resistance and high frequency performance

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.620 in (41.15 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR0.090 Ohm/1000ft (0.30 Ohm/km)

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Inductance Cond-GrndNom. InductanceNom. Velocity of Prop.Max. Current
Conductor(s)0.047 Ohm/1000ft (0.15 Ohm/km)33 pF/ft (110 pF/m)60 pF/ft (200 pF/m)56 Ohm0.055 μH/ft0.136 μH/ft (0.446 μH/m)55%260 Amps per Conductor at 30oC
Segmented Ground Wire0.05 Ohm/1000ft (0.16 Ohm/km)
Cable

Voltage

UL Voltage Rating1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)

Mechanical Characteristics

Max. Pull Tension10048 lbs (4557.7 kg)
Bulk Cable Weight3185 lbs/1000ft (4740 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C

Bend Radius

Stationary Min.16.2 in (411 mm)
Installation Min.19.4 in (493 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, FT4, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, WTTC, XHHW-2, UL Flexible Motor Supply Cable
CEC / C(UL) ComplianceTC.
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)P-07-KA070003-MSHA

History

Update and RevisionRevision Number: 0.733 Revision Date: 06-30-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.