Belden Store
29529

Product Number: 29529

VFD 100% Gnd, 3C #1/0 Str TC XLPE Ins + #1/0 Symm. Seg. Gnd (3 of #4) Str BC, CTS, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC

Belden 100% Ground Flexible VFD, 3 Conductor 1/0AWG (7x19x21) Tinned Copper XLPE Insulation M4 Color Code + 1/0AWG Symmetrical Segmented Ground (3 of 4AWG) Bare Copper Stranded in Continuous Contact with Overall Dual Copper Tape Helically Applied Shield, Black PVC Outer Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC 1000V CSA AWM I/II A/B 600V RW90 TC SUN RES DIR BUR Oil Resistant

Availability
Global
Status
Active
Orderable items
3

Ships from and sold by A5 IT.

Part numbers

29529 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCFootnoteOrder
29529 010500BlackReel500 ft612825137986C 9Order online
29529 0102000BlackReel2,000 ft612825137955C ZOrder online
29529 0102500BlackReel2,500 ft612825137979C ZOrder online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.741 Revision Date: 06-30-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN., 9 - FINAL PUT-UP LENGTH MAY VARY (+ OR -) 5% FROM LENGTH SHOWN.

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC150A1501RA

Construction Details

Overall Cable Diameter (Nominal)1.258 in (31.95 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)31/0 AWG7x19x21TC - Tinned CopperFinely Stranded Tinned Copper Optomized for VFD Use
Segmented Ground Wire34 AWG7x19x25BC - Bare CopperSegmented Grounds (3 Totaling 1/0)

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.057 in (1.4 mm)0.501 in (12.7 mm)ICEA Chart M4
Ground WireNo Insulation

Outer Shield

Shield TypeMaterialCoverageNotes
Helical TapeBare Copper (BC)100%2 mil Helical Copper Tape for Crack Resistance and High Frequency Noise Conduction
Helical TapeBare Copper (BC)100%2 mil Helical Copper Tape for Crack Resistance and High Frequency Noise Conduction

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.083 in (2.1 mm)
Nom. Diameter1.258 in (31.95 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR0.40 Ohm/1000ft (1.3 Ohm/km)

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Inductance Cond-GrndNom. Velocity of Prop.Max. Current
Conductor(s)0.094 Ohm/1000ft (0.31 Ohm/km)37 pF/ft (120 pF/m)67 pF/ft (220 pF/m)50 Ohm0.072 μH/ft55%170 Amps per Conductor at 30oC
Segmented Ground Wire0.09 Ohm/1000ft (0.30 Ohm/km)

Voltage

UL Voltage Rating1000 V (TC, WTTC, UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC)

Mechanical Characteristics

Max. Pull Tension5530 lbs (2510 kg)
Bulk Cable Weight1708 lbs/1000ft (2542 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C

Bend Radius

Stationary Min.12.5 in (318 mm)
Installation Min.15.1 in (384 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, FT4, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, WTTC, XHHW-2, UL Flexible Motor Supply Cable
CEC / C(UL) ComplianceTC.
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)P-07-KA070003-MSHA

History

Update and RevisionRevision Number: 0.741 Revision Date: 06-30-2026
FootnoteC - CRATE REEL PUT-UP., Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN., 9 - FINAL PUT-UP LENGTH MAY VARY (+ OR -) 5% FROM LENGTH SHOWN.

Resources

Related vfd cable