Belden Store
29524C

Product Number: 29524C

VFD, 3C #8 Str BC XLPE Ins + #10 Symm. Seg. Gnd (3 of #14) Str BC, CTS, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V

Belden Basics VFD, 3 Conductor 8AWG (7x16) Bare Copper XLPE Insulation M4 Color Code + 10AWG Symmetrical Segmented Ground (3 of 14AWG) Bare Copper Stranded in Continuous Contact with Overall Dual Copper Tape Helically Applied Shield, Black PVC Outer Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V SUN RES DIR BUR Oil Resistant

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

29524C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthUPCOrder
29524C 0105000BlackReel5,000 ft612825137726Order online

Specifications

Information

Put-Up TypeReel
Update and RevisionRevision Number: 0.742 Revision Date: 04-01-2026

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; Class 1 Division 2 Hazardous Locations

Construction Details

Overall Cable Diameter (Nominal)0.646 in (16.4 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterialNotes
Conductor(s)38 AWG7x16BC - Bare CopperASTM B3 Copper B8 Class B Stranding
Segmented Ground Wire314 AWG7x22BC - Bare CopperSegmented Ground (3 Totaling 10+ AWG)

Insulation

ElementMaterialNom. ThicknessNom. Insulation DiameterColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.047 in (1.2 mm)0.236 in (5.99 mm)ICEA Chart M4
Ground WireNo Insulation

Outer Shield

Shield TypeMaterialCoverage
Helical TapeBare Copper (BC)100%
Helical TapeBare Copper (BC)100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.063 in (1.6 mm)
Nom. Diameter0.646 in (16.4 mm)
RipcordYes

Electrical Characteristics

Nom Outer Shield DCR0.81 Ohm/1000ft (2.7 Ohm/km)

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Capacitance Cond-to-Other (Conds + Shield)Nom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Conductor(s)0.564 Ohm/1000ft (1.85 Ohm/km)31 pF/ft (100 pF/m)63 pF/ft (210 pF/m)50 Ohm55%55 Amps per Conductor at 30oC
0.90 Ohm/1000ft (3.0 Ohm/km)

Voltage

UL Voltage Rating600 / 1000 V (TC-ER)

Mechanical Characteristics

Max. Pull Tension678 lbs (308 kg)
Bulk Cable Weight350 lbs/1000ft (520 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-40°C To +90°C

Bend Radius

Stationary Min.7.8 in (200 mm)
Installation Min.7.8 in (200 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL 1685 UL Loading, IEEE 1202 FT4
NEC / UL ComplianceArticle 336, TC-ER, XHHW-2
ICEA ComplianceS-95-658
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)P-07-KA070003-MSHA

History

Update and RevisionRevision Number: 0.742 Revision Date: 04-01-2026

Resources

Related vfd cable