VFD, 3C #8 Str TC XLPE Ins + #14 Symm. Seg. Gnd (3 of #14) Str BC, CTS, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B
Belden Premium VFD, 8 AWG (7 x 19 x 29) Tinned Copper, 3 Conductor, XLPE Insulation M4 Color Code, With 3 #14 AWG (41 x 30) Bare Copper Ground Wire in Continuous Contact with Overall Copper Tape Helically Applied Shield, Black Outer PVC Jacket, 600/1000V TC-ER 90C Dry/Wet 1000V, CSA AWM I/II A/B Sun Res Dir Bur Oil Resistant.
- Availability
- Global
- Status
- Active
Specifications
Product Overview
| Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems; Class 1 Division 2 Hazardous Locations; Recommended Cable Gland Belden BTC100A0791RA |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.697 in (17.7 mm) |
|---|
Conductor
| Element | Size | Stranding | Material | Notes |
|---|---|---|---|---|
| Conductor(s) | 8 AWG | 7x19x29 | TC - Tinned Copper | ASTM B3 Copper B8 Class B Stranding |
| Segmented Ground Wire | 14 AWG | 41x30 | BC - Bare Copper | Segmented Ground (3 Totaling 10+ AWG) |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.47 in | 0.26 in (6.6 mm) | ICEA Chart M4 |
| Ground Wire | No Insulation |
Outer Shield
| Shield Type | Material | Coverage | Notes |
|---|---|---|---|
| Tape | Bare Copper (BC) | 100% | 2 mil Copper Tape |
| Bare Copper (BC) |
Outer Jacket
| Material | XLPE - Cross-Linked Polyethylene (Thermoset) |
|---|---|
| Nom. Thickness | 0.063 in mm |
| Nom. Diameter | 0.697 in (17.7 mm) |
| Ripcord | Yes |
Electrical Characteristics
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Other (Conds + Shield) | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|---|---|---|---|---|---|
| Conductor(s) | 0.564 Ohm/1000ft (1.85 Ohm/km) | 31 pF/ft (100 pF/m) | 63 pF/ft (210 pF/m) | 50 Ohm | 55% | 55 Amps per Conductor at 30oC |
| 0.90 Ohm/1000ft (3.0 Ohm/km) |
Voltage
| UL Voltage Rating | 600/1000 V (TC-ER) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 678 lbs (308 kg) |
|---|---|
| Bulk Cable Weight | 350 lbs/1000ft (520 kg/km) |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | -20°C To +90°C |
Bend Radius
| Stationary Min. | 5.23 in (133 mm) |
|---|---|
| Installation Min. | 5.23 in |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|---|
| Sustainability | CA Prop 65 |
| Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, TC-ER, XHHW-2 |
| ICEA Compliance | S-95-658 |
| European Directive Compliance | EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| Other Standard Compliance(s) | P-07-KA070003-MSHA |
History
| Update and Revision | Revision Number: 0.50 Revision Date: 04-02-2026 |
|---|
Resources
Related vfd cable

29500
VFD 300% Gnd, 3C+G #16 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#16 TC Ground/Drain, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
PVC - Polyvinyl Chloride · 600 V RMS (Type TC) (TC-ER, WTTC, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) · 90°C Dry, 90°C Wet

29500T
VFD 300% Gnd, 3C+G #16 Str TC, XLPE Ins+PVC Grd, OS+TC Brd w/#16 TC Drain, Blk LSZH Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
LSZH - Low Smoke Zero Halogen (Flame Retardant) · 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) · 90°C Dry, 90°C Wet

29501
VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#14 TC Ground/Drain, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
PVC - Polyvinyl Chloride · 1000 V (TC-ER, WTTC,UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) · 90°C Dry, 90°C Wet

29501T
VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Grd, OS+TC Brd w/#14 TC Drain, Blk LSZH Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
LSZH - Low Smoke Zero Halogen (Flame Retardant) · 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) · 90°C Dry, 90°C Wet