VFD, 3C #16 Str BC XLPE Ins + #14 Symm. Seg. Gnd (3 of #18) Str BC, CTS, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B
Belden Basics VFD, 3 Conductor 16AWG (7x24) Bare Copper XLPE Insulation M4 Color Code + 14AWG Symmetrical Segmented Ground (3 of 18AWG) Bare Copper Stranded, Overall Dual Copper Tape Helically Applied Shield, Black PVC Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN RES DIR BUR Oil Resistant
- Availability
- Global
- Status
- Active
- Orderable items
- 2
Part numbers
29520C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.
| Item # | Color | Putup Type | Length | UPC | Order |
|---|---|---|---|---|---|
| 29520C 0101000 | Black | Reel | 1,000 ft | 612825137627 | Order online |
| 29520C 0105000 | Black | Reel | 5,000 ft | 612825137634 | Order online |
Specifications
Information
| Put-Up Type | Reel |
|---|---|
| Update and Revision | Revision Number: 0.734 Revision Date: 04-01-2026 |
Product Overview
| Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems;Class 1 Division 2 Locations |
|---|
Construction Details
| Overall Cable Diameter (Nominal) | 0.397 in (10.1 mm) |
|---|
Conductor
| Element | No. of Elements | Size | Stranding | Material | Notes |
|---|---|---|---|---|---|
| Conductor(s) | 3 | 16 AWG | 7x24 | BC - Bare Copper | ASTM B3 Copper B8 Class B Stranding |
| Segmented Ground Wire | 3 | 18 AWG | 7x26 | BC - Bare Copper | 3 Ground Segments Totaling 14 AWG |
Insulation
| Element | Material | Nom. Thickness | Nom. Insulation Diameter | Color Code |
|---|---|---|---|---|
| Conductor(s) | XLPE - Cross-Linked Polyethylene (Thermoset) | 0.031 in (0.79 mm) | 0.123 in (3.12 mm) | ICEA Chart M4 |
| Ground Wire | No Insulation |
Outer Shield
| Shield Type | Material | Coverage |
|---|---|---|
| Helical Tape | Bare Copper (BC) | 100% |
| Helical Tape | Bare Copper (BC) | 100% |
Outer Jacket
| Material | PVC - Polyvinyl Chloride |
|---|---|
| Nom. Thickness | 0.060 in (1.5 mm) |
| Nom. Diameter | 0.397 in (10.1 mm) |
| Ripcord | Yes |
Electrical Characteristics
| Nom Outer Shield DCR | 1.90 Ohm/1000ft (6.23 Ohm/km) |
|---|
Electricals
| Element | Nom. Conductor DCR | Nom. Capacitance Cond-to-Cond | Nom. Capacitance Cond-to-Shield | Nom. Characteristic Impedence | Nom. Velocity of Prop. | Max. Current |
|---|---|---|---|---|---|---|
| Conductor(s) | 3.91 Ohm/1000ft (12.8 Ohm/km) | 25 pF/ft (82 pF/m) | 48 pF/ft (160 pF/m) | 50 Ohm | 55% | 18 Amps per Conductor at 30oC |
| 1.60 Ohm/1000ft (5.25 Ohm/km) |
Voltage
| UL Voltage Rating | 600 V (TC-ER) |
|---|
Mechanical Characteristics
| Max. Pull Tension | 130 lbs (59 kg) |
|---|---|
| Bulk Cable Weight | 116 lbs/1000ft (173 kg/km) |
Temperature
| UL Temperature | 90°C Dry, 90°C Wet |
|---|---|
| Operating | -40°C To +90°C |
Bend Radius
| Stationary Min. | 4.8 in (120 mm) |
|---|---|
| Installation Min. | 4.8 in (120 mm) |
Standards and Compliance
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Burial |
|---|---|
| Sustainability | CA Prop 65 |
| Flammability / Reaction to Fire | UL 1685 UL Loading, IEEE 1202 FT4 |
| NEC / UL Compliance | Article 336, TC-ER |
| ICEA Compliance | S-95-658 |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
History
| Update and Revision | Revision Number: 0.734 Revision Date: 04-01-2026 |
|---|
Resources
Related vfd cable

29500
VFD 300% Gnd, 3C+G #16 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#16 TC Ground/Drain, Blk PVC Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
PVC - Polyvinyl Chloride · 600 V RMS (Type TC) (TC-ER, WTTC, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) · 90°C Dry, 90°C Wet

29500T
VFD 300% Gnd, 3C+G #16 Str TC, XLPE Ins+PVC Grd, OS+TC Brd w/#16 TC Drain, Blk LSZH Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
LSZH - Low Smoke Zero Halogen (Flame Retardant) · 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) · 90°C Dry, 90°C Wet

29501
VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#14 TC Ground/Drain, Blk PVC Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
PVC - Polyvinyl Chloride · 1000 V (TC-ER, WTTC,UL44, UL Flexible Motor Supply Cable), 600 V (C(UL) CIC TC) · 90°C Dry, 90°C Wet

29501T
VFD 300% Gnd, 3C+G #14 Str TC, XLPE Ins+PVC Grd, OS+TC Brd w/#14 TC Drain, Blk LSZH Jkt, 600/1000V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable WTTC
LSZH - Low Smoke Zero Halogen (Flame Retardant) · 1000 V (TC, WTTC, UL Flexible Motor Supply Cable) · 90°C Dry, 90°C Wet