Belden Store
DEDN188F

Product Number: DEDN188F

Indoor/Outdoor Digital ElectricityTM, 8 Pr #18 Str TC, O/A Foil, PVC Jkt, CL4, CMG, Wet Locations

Indoor/Outdoor Digital ElectricityTM Copper Cable, 8 Twisted Pair 18 AWG (7 x 26) Stranded Tinned Copper, PVC Insulation, Overall foil shield, Black PVC Jacket, Ripcord, CL4, CMG, Wet Locations, 2000 Ft Reel

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

DEDN188F is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorLengthOrder
DEDN188FBlack2,000 ftOrder online

Specifications

Product Overview

Suitable ApplicationsDigital ElectricityTM, Fault Managed Power Systems (FMPS), remote powering, wet locations, in-conduit

Construction Details

Conductor

Size18
Stranding7x26
MaterialTC - Tinned Copper

Insulation

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.017 in (0.43 mm)
Color CodeBlack & Red, Black & White, Black & Green, Black & Blue, Black & Yellow, Black & Brown, Black & Orange, Red & White

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.040 in (1.0 mm)
Nom. Diameter0.524 in (13.3 mm)

Electrical Characteristics

Nom Outer Shield DCR7.1 Ohm/1000ft (23 Ohm/km)

Electricals

Nom. Conductor DCR6.4 Ohm/1000ft
Nom. Capacitance Cond-to-Cond26.75 pF/ft (87.76 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)28 pF/ft (92 pF/m)
Max. Current4 Amps per Conductor at 25oC (35°C Temperature Rise)

Voltage

UL Voltage Rating450 V RMS

Mechanical Characteristics

Max. Pull Tension360 lbs (160 kg)
Bulk Cable Weight157 lbs/1000ft

Temperature

UL Temperature105°C
Operating-30°C To +105°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
Flammability / Reaction to FireUL 1685 FT4 Loading, FT4
NEC / UL ComplianceArticle 725, Article 800, CL4-FMP (2.5A), CL3, CMG
AWM ComplianceAWM 2464
CEC / C(UL) ComplianceCMG.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE), REACH: 2020-01-28
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.111 Revision Date: 09-07-2025

Resources

Related fault-managed power system (fmps) cables