Belden Store
DEDN182F

Product Number: DEDN182F

Indoor/Outdoor Digital ElectricityTM, 2 Pr #18 Str TC, O/A Foil, PVC Jkt, CL4, CMG, Wet Locations

Indoor/Outdoor Digital ElectricityTM Copper Cable, 2 Twisted Pair 18 AWG (7 x 26) Stranded Tinned Copper, PVC Insulation, Overall foil shield, Black PVC Jacket, Ripcord, CL4, CMG, Wet Locations, 2000 Ft Reel

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

DEDN182F is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorLengthOrder
DEDN182FBlack2,000 ftOrder online

Specifications

Product Overview

Suitable ApplicationsDigital ElectricityTM, Fault Managed Power Systems (FMPS), remote powering, wet locations, in-conduit

Construction Details

Conductor

Size18
Stranding7x26
MaterialTC - Tinned Copper

Insulation

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.017 in (0.43 mm)
Color CodeBlack & Red, Black & White

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.032 in (0.81 mm)
Nom. Diameter0.356 in (9.04 mm)

Electrical Characteristics

Nom Outer Shield DCR7.4 Ohm/1000ft (24 Ohm/km)

Electricals

Nom. Conductor DCR6.4 Ohm/1000ft (21 Ohm/km)
Nom. Capacitance Cond-to-Cond29.25 pF/ft (95.96 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)52.5 pF/ft (172 pF/m)

Voltage

UL Voltage Rating450 V RMS

Mechanical Characteristics

Max. Pull Tension90 lbs (41 kg)
Bulk Cable Weight53 lbs/1000ft

Temperature

UL Temperature105°C
Operating-30°C To +105°C

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
Flammability / Reaction to FireUL 1685 FT4 Loading, FT4
NEC / UL ComplianceArticle 725, Article 800, CL4-FMP (2.5A), CL3, CMG
AWM ComplianceAWM 2464
CEC / C(UL) ComplianceCMG.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE), REACH: 2020-01-28
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.52 Revision Date: 09-07-2025

Resources

Related fault-managed power system (fmps) cables