Belden Store
C4G2.5SY

Product Number: C4G2.5SY

MachFlexTM 375SY Control Cable, 3 C + 1 G 2.5 mm2 Str BC, PVC Ins, PVC Inner Jkt, GSWB, PVC Outer Jkt

MachFlexTM 375SY Control Cable, 3 Conductor + 1 Ground 2.5 mm2 Stranded Bare Copper, PVC Insulation, PVC Inner Jacket, Galvanized Steel Wire Braid, PVC Outer Jacket

Availability
EMEA | Asia Pacific
Status
Active
Orderable items
10

Ships from and sold by A5 IT.

Part numbers

C4G2.5SY is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorLengthOrder
C4G2.5SY 010100MBlack, RAL 9004100 mOrder online
C4G2.5SY 010200MBlack, RAL 9004200 mOrder online
C4G2.5SY 010300MBlack, RAL 9004300 mOrder online
C4G2.5SY G8U100MGray, RAL 7001100 mOrder online
C4G2.5SY G8U200MGray, RAL 7001200 mOrder online
C4G2.5SY G8U300MGray, RAL 7001300 mOrder online
C4GESY-KC50Transparent50 mOrder online
C4G2.5SY 368100MTransparent100 mOrder online
C4G2.5SY 368200MTransparent200 mOrder online
C4G2.5SY 368300MTransparent300 mOrder online

Specifications

Product Overview

Suitable ApplicationsDesigned for applications which are installed in occasional flexing and fixed locations. Cable applications include precision control sensors, multi axis control machines, temperature controllers, control panels, machine cutting tools, auxiliary equipment, motor speed control, production machinery and many more. Galvanized steel wire braid armor provides excellent mechanical protection.

Construction Details

Overall Cable Diameter (Nominal)13.9 mm (0.547 in)

Conductor

ElementNo. of ElementsSizeStrandingStranding ClassMaterial
Conductor(s)32.5 mm2StrandedClass 5BC - Bare Copper
Ground12.5 mm2StrandedClass 5BC - Bare Copper

Insulation

ElementMaterialColor Code
Conductor(s)PVC - Polyvinyl ChlorideBrown, Black, Grey
GroundPVC - Polyvinyl ChlorideYellow/Green

Inner Jacket

MaterialPVC - Polyvinyl Chloride

Armor

Armor Type & MaterialSWB - Steel Wire Braid Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride

Electrical Characteristics

Voltage

Voltage Rating450/750 V (Max. Operating Voltage), 4000 V (Testing Voltage)

Mechanical Characteristics

Bulk Cable Weight295 kg/km (198 lbs/1000ft)

Temperature

Operating-5°C to +70°C (Occasional movement)
Installation-40°C to +80°C (Fixed installation)

Bend Radius

Installation Min.83.4 mm (3.28 in)
Flexing Min.278 mm

Standards and Compliance

Environmental SuitabilitySunlight Resistance, UV Resistance, Oil Resistance - EN 50290-2-22 (TM54)
Flammability / Reaction to FireIEC 60332-1-2, DIN VDE 0482-332-1-2, DIN EN 60332-1-2
ISO/IEC ComplianceIEC 60228, IEC 60227-5
CENELEC ComplianceEN 50290-2-22
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2)
Other Standard Compliance(s)VDE 0295, DIN VDE 0207-363-4-1, EN 50525-2-51, BS 6360

Product Notes

NotesEMEA PN : C4GESY

History

Update and RevisionRevision Number: 0.36 Revision Date: 01-15-2026