Belden Store
GCRJCI20

Product Number: GCRJCI20

Universal OFC MLT (jelly filled) : GLASS YARNS + LSZH with 12 Tubes of Ø1.9mm 120f SM OS2 G.657.B3. CPR Cca.

Universal (Indoor/Outdoor) optical fiber Multi Loose Tube (jelly filled tube) cable with glass yarns as strength member and Low Smoke Zero Halogen outer jacket. Product feature: This cable has rodent protection by glass yarns. Existing out of 12 tubes with a diameter of 1.9mm with 120 fibers (10t x 12f) SM OS2 G.657.B3. CPR Euroclass Cca.

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Environmental SpaceIndoor/Outdoor - Euroclass Cca
Suitable ApplicationsFor outdoor and indoor use in structured (data) wiring systems such as industrial backbone, campus backbone, building backbone (riser) and/or horizontal cabling. For outdoor and indoor use in networks for industrial, telecom, cable TV and/or broadcast. Easy to install in ducts, tunnels and/or tubes.

Construction

Fiber Color CodeTIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua
Central Strength Member TypeGRP
Cable Core Water TightYes
Cable Core Water BlockingWaterblocking Glass Yarns + Tape
Bulk Cable Weight291 kg/km

Fiber Cable Construction

Fiber TypeOS2
Fiber Grade acc. ITU-TG.657.B3
Fiber Count120
Subunit ColorTIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet

SubUnit Specifications

Number of Active Subunits10
Number of Subunit Positions12
Fibers Per Subunit12

Physical Specifications

Type of ArmorNon-Armored

Jacket Specifications

Number of JacketsSingle Jacket

Outer Jacket Specifications

Outer Jacket1 Table NotesStandard color: Orange. Available colors: Orange, Yellow, Turquoise, Erika Violet, Red, Blue, Green, Brown, Violet, Pink, Grey, White, Black, Lime Green

Outer Jacket

MaterialLSZH - Low Smoke Zero Halogen (Flame Retardant)
ColorBlack
Nominal Diameter16.6 mm
RipcordYes

Optical Characteristics

Maximum Attenuation at 1310 nm0.39 dB/km
Maximum Attenuation at 1550 nm0.24 dB/km
Maximum Attenuation at 1625 nm0.29 dB/km

Mechanical Characteristics

Mechanical Tests

DescriptionTested StandardRequirement/ValueAccording to Family Specification
Cable Min. Bend Radius Installation (Short Term)IEC 60794-1-21-E6312 mmIEC 60794-3-10
Cable Min. Bend Radius Operation (Long Term)IEC 60794-1-21-E11234 mmIEC 60794-3-10
Cable Max. Tensile Strength Installation (Short Term)IEC 60794-1-21-E16000 N (1349 lbf)IEC 60794-3-10
Cable Max. Tensile Strength Operation (Long Term)IEC 60794-1-21-E12000 N (450 lbf)IEC 60794-3-10
Cable Max. Crush Resistance Installation (Short Term)IEC 60794-1-21-E315 kN/mIEC 60794-3-10
Cable Max. Crush Resistance Operation (Long Term)IEC 60794-1-21-E37.5 kN/mIEC 60794-3-10
Cable Impact ResistanceIEC 60794-1-21-E410 J, 300 mm Radius, 3 CyclesIEC 60794-3-10
Cable Torsion ResistanceIEC 60794-1-21-E7180°, 2 m, 10 cyclesIEC 60794-3-10
WaterblockingIEC 60794-1-22-F5

Temperature Range

Operating Temperature Range-30 °C to +70 °C
Installation Temperature Range-5 °C to +50 °C
Storage Temperature Range-30 °C to +70 °C

Product Material

UL Rating/Flame TestNon-UL Rated

Standards

IEC 60754-2 - Halogen Acid Gas Amount - Max. Conductivity10 μS/mm
IEC FlammabilityIEC 60332-1-2
IEC 60754-2 - Halogen Acid Gas Amount - Min. pH4.3
Reaction to Fire - Bundle Flame TestIEC 60332-3-24
IEC 60754-1 - Halogen AmountZero
IEC 61034-2 - Smoke Density Min. Transmittance60%
CPR EuroclassCca-s1,d1,a1
REACHCompliant
ISO/IEC ComplianceIEC 60794, ISO/IEC 11801-1
UV/ Sunlight ProtectionYes

History

Update and RevisionRevision Number: 0.11 Revision Date: 12-03-2025

Resources

Related multi-loose tube fiber cable