Indoor Mini-distribution 24 Fibers OM4
Indoor Mini-distribution fiber cable, OM4, 24F, LSZH Jacket, IEC 60332-3-24
- Availability
- Asia Pacific
- Status
- Active
Specifications
Product Overview
| Environmental Space | Indoor |
|---|---|
| Suitable Applications | High degree of flexibility suitable for horizontal, interconnect applications; Excellent LSZH flame retardant performance for indoor application |
Construction
| Fiber Color Code | TIA coding (Gxxxxxx.T): Blue, Orange, Green, Brown, Gray, White, Red, Black, Yellow, Violet, Pink, Aqua |
|---|---|
| Central Strength Member Type | GRP |
| Bulk Cable Weight | 36 kg/km |
Fiber Cable Construction
| Fiber Type | OM4 |
|---|---|
| Fiber Count | 24 |
| Subunit Color | Erika Violet |
SubUnit Specifications
| Number of Active Subunits | 2 |
|---|
Physical Specifications
| Number Of Fillers @Stranding1 | 2 |
|---|---|
| Type of Armor | Non-Armored |
Jacket Specifications
| Number of Jackets | Single Jacket |
|---|
Outer Jacket Specifications
Outer Jacket
| Material | LSZH - Low Smoke Zero Halogen (Flame Retardant) |
|---|---|
| Nominal Diameter | 6.5 mm |
| Nominal Wall Thickness | 0.65 mm |
Optical Characteristics
| Fiber Core Diameter | 50 ±2.5 μm |
|---|---|
| Maximum Attenuation at 1300 nm | 1.0 dB/km |
| Maximum Attenuation at 850 nm | 3.0 dB/km |
Mechanical Characteristics
Mechanical Tests
| Description | Tested Standard | Requirement/Value |
|---|---|---|
| Cable Min. Bend Radius Installation (Short Term) | IEC 60794-1-21-E11 | 20 x Cable OD |
| Cable Min. Bend Radius Operation (Long Term) | IEC 60794-1-21-E11 | 10 x Cable OD |
| Cable Max. Tensile Strength Installation (Short Term) | IEC 60794-1-21-E1 | 660 N (148 lbf) |
| Cable Max. Tensile Strength Operation (Long Term) | IEC 60794-1-21-E1 | 200 N (45 lbf) |
| Cable Max. Crush Resistance Installation (Short Term) | IEC 60794-1-21-E3 | 1000 N/100mm |
Temperature Range
| Operating Temperature Range | -20 °C to +60 °C |
|---|---|
| Storage Temperature Range | -20 °C to +60 °C |
Product Material
| UL Rating/Flame Test | Non-UL Rated |
|---|
Standards
| IEC Flammability | IEC 60332-3-24 |
|---|---|
| TIA/EIA Compliance | EIA/TIA-455 |
| ISO/IEC Compliance | IEC 60793-1-1, IEC 60794-1-1 |
History
| Update and Revision | Revision Number: 0.23 Revision Date: 12-07-2023 |
|---|
Resources
Related mini distribution fiber cable

AX110185-xxxM
FMT I/O OM4 MPO12(M-O) 48F xxxM OFCP MD_3.0 1.0xIL BK_JKT AQ_SUB

FD1M006P0
Indoor/Outdoor Mini-Distribution OM1 6 Fibers OFNP Double Jacket 6.7mm
PVC - Polyvinyl Chloride
1 item
BeldenFD1M006P2
FD1M006P2
Indoor/Outdoor Plenum OM1 Mini-Distribution 6F
1 item
BeldenFD1M012P2
FD1M012P2
Indoor/Outdoor Plenum OM1 Mini-Distribution 12F 3mm Sub-Units
1 item