Belden Store
123106A

Product Number: 123106A

RS-485, 1 Pr, 22AWG, Str TC, PE Ins, with OS, 1C 22AWG Str, PVC Ins, OA TC Brd, PVC Jkt, AIA, PVC Jkt, CM, PLTC, Sun Res

RS-485, 120 Ohm, 1 pair 22AWG (7x30) tinned copper Datalene® insulaton, with Foil Shield, 1 Conductor 22AWG (7x30) Tinned Copper, PVC Insulated, Overall 65% Tinned Copper Braid, PVC jacket, Aluminum Interlock Armor, PVC Jacket, CM, PLTC, SUN RES

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable Applicationsexposure to rodent, crush, or cut through force, burial, serial communication (RS-485 standard) comprising of PLCs, VFDs, HMIs, motors, RTU, SCADA, etc. within noisy environments over long distance, outdoor such as solar, lighting, etc.

Construction Details

Overall Cable Diameter (Nominal)0.593 in (15.1 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Pair(s)122 AWG7x30TC - Tinned Copper
Conductor(s)122 AWG7x30TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessColor CodeNotes
Pair(s)PE - Polyethylene (Foam)0.033 in (0.84 mm)White/Orange Stripe & Orange/White StripeHDPE
Conductor(s)PVC - Polyvinyl Chloride0.017 in (0.43 mm)Blue/White Stripe

Inner Shield

ElementPair(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
NotesSingle conductor is not under tape

Outer Shield

Shield TypeMaterialCoverageDrainwire Type
TapeBi-Laminate (Alum+Poly)100%22 AWG (7x30) TC
BraidTinned Copper (TC)65%

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Diameter0.300 in (7.62 mm)

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.045 in (1.1 mm)
Nom. Diameter0.593 in (15.1 mm)

Electrical Characteristics

Nom Outer Shield DCR2.8 Ohm/1000ft (9.2 Ohm/km)

Electricals

ElementNom. Conductor DCRNom. Capacitance Cond-to-CondNom. Characteristic ImpedenceNom. Velocity of Prop.Max. Current
Pair(s)14.7 Ohm/1000ft (48.2 Ohm/km)11 pF/ft (36 pF/m)120 Ohm78%2.7 Amps per Conductor at 25oC
Conductor(s)14.7 Ohm/1000ft (48.2 Ohm/km)

High Frequency (Nominal/Typical)

ElementPair(s)
Frequency [MHz]1
Nom. Insertion Loss (Attenuation)0.5 dB/100ft

Voltage

UL Voltage Rating300 V (CM, PLTC)

Mechanical Characteristics

Temperature Table Notes-40C
Max. Pull Tension200 lbs (91 kg)
Bulk Cable Weight150 lbs/1000ft (220 kg/km)

Temperature

UL Temperature60°C
Operating-40°C to +60°C

Bend Radius

Stationary Min.7.1 in (180 mm)
Installation Min.7.1 in

Standards and Compliance

Environmental SuitabilityIndoor, Sunlight Resistance
Flammability / Reaction to FireUL1685 UL Loading, 1202
NEC / UL ComplianceArticle 725, Article 800
CEC / C(UL) ComplianceCMG HLBCD.
European Directive ComplianceEU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)

History

Update and RevisionRevision Number: 0.74 Revision Date: 05-05-2023

Resources