Belden Store
BeldenM39111

Product Number: M39111

CONTROL, 2C #14, Str, PVC/NYLON, 600 V, TC 90C, SUN RES, DIRECT BURIAL

CONTROL, 2 Conductor 14 AWG (41/30) TC - Tinned Copper, PVC/NYLON Insulation, Overall Aluminum/Polyester Shield, Black PVC Outer Jacket, TC 90C, SUN RES, DIRECT BURIAL

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

M39111 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthOrder
M39111 BK001BlackReel1,000 ftOrder online

Specifications

Product Overview

Suitable ApplicationsData, communication, audio, and low-level signal transmission; industrial networking, serial communication, control panels, automation equipment, and instrumentation systems.

Construction Details

Overall Cable Diameter (Nominal)0.357 in (9.07 mm)

Conductor

ElementConductor(s)
No. of Elements2
Size14 AWG
Stranding41x30
MaterialTC - Tinned Copper

Insulation

ElementConductor(s)
MaterialPVC/Nylon - Polyvinyl Chloride + Nylon
Nom. Thickness0.022 in (0.56 mm)
Nom. Insulation Diameter0.127 in (3.23 mm)
Color CodeBlack, Red

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type16 AWG (19x29) TC

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.048 in (1.2 mm)
Nom. Diameter0.357 in (9.07 mm)

Electrical Characteristics

Nom Outer Shield DCR38 Ohm/1000ft (120 Ohm/km)

Electricals

ElementConductor(s)
Nom. Capacitance Cond-to-Cond46 pF/ft (150 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)83 pF/ft (270 pF/m)
Nom. Characteristic Impedence45 Ohm
Nom. Inductance0.18 μH/ft (0.59 μH/m)

Voltage

UL Voltage Rating600 V (TC)

Mechanical Characteristics

Max. Pull Tension60 lbs (27 kg)

Temperature

UL Temperature90°C
Operating-25°C To +90°C

Bend Radius

Stationary Min.3.6 in (91 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Sunlight Resistance, Burial
SustainabilityCA Prop 65
NEC / UL ComplianceArticle 336, TC
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlpha Wire -* P/N M39111 2C 14 AWG EXXXXXX (UL) TYPE TC 600V 90C DRY 75C WET SUN RES DIR BUR CE ROHS

History

Update and RevisionRevision Number: 0.15 Revision Date: 06-30-2026

Resources

Related multi-conductor cable