Belden Store
Belden77026

Product Number: 77026

ECOCABLE, 12C #18, Str, MPPE, 600 V, AWM/STYLE 11231 105C, AWM/STYLE 21915 105C, Horizontal Flame, CSA C(RU) AWM I/II A/B FT2

ECOCABLE, 12 Conductor 18 AWG (16/30) TC - Tinned Copper, MPPE Insulation, Slate MPPE Outer Jacket, AWM/STYLE 11231 105C, AWM/STYLE 21915 105C, Horizontal Flame, CSA C(RU) AWM I/II A/B FT2 C(RU) AWM I/II A/B FT2

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

77026 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthOrder
77026 SL005SlateReel100 ftOrder online

Specifications

Product Overview

Suitable ApplicationsData, communication, audio, and low-level signal transmission; industrial networking, serial communication, control panels, automation equipment, and instrumentation systems.

Construction Details

Overall Cable Diameter (Nominal)0.355 in (9.02 mm)

Conductor

ElementConductor(s)
No. of Elements12
Size18 AWG
Stranding16x30
MaterialTC - Tinned Copper

Insulation

ElementConductor(s)
MaterialmPPE - Modified Polyphenylene Ether
Nom. Thickness0.012 in (0.30 mm)
Nom. Insulation Diameter0.069 in (1.8 mm)
Color CodeBlack, Brown, Red, Orange, Yellow, Green, Blue, Violet, Slate, White, White/Black, White/Brown

Outer Jacket

MaterialmPPE - Modified Polyphenylene Ether
Nom. Thickness0.032 in (0.81 mm)
Nom. Diameter0.355 in (9.02 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Capacitance Cond-to-Cond17.8 pF/ft (58.4 pF/m)
Nom. Inductance0.17 μH/ft (0.56 μH/m)

Voltage

UL Voltage Rating600 V (AWM 11231, AWM 21915), 600 V (CSA AWM)

Mechanical Characteristics

Max. Pull Tension155 lbs (70.3 kg)

Temperature

UL Temperature105°C
Operating-50°C To +105°C

Bend Radius

Stationary Min.3.5 in (89 mm)

Standards and Compliance

Environmental SuitabilityIndoor
SustainabilityCA Prop 65
Flammability / Reaction to FireFT2
AWM ComplianceAWM 21915, AWM I/II A/B
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlpha Wire -* P/N 77026 12C 18 AWG ECOCABLE(R) RU AWM 21915 105C 600V C(RU) AWM I/II A/B FT2 600V 105C CE ROHS (SEQ FOOTAGE)

History

Update and RevisionRevision Number: 0.15 Revision Date: 06-30-2026

Resources