Product Number: 58643

Communication and Control, 3PR #16, Str, FEP, 150 V, CMP 125C, CSA FT6, CSA C(UL) TYPE CMP

Communication and Control, 3 Pair 16 AWG (7/.0192) TC - Tinned Copper, FEP Insulation, Slate PVDF Outer Jacket, CMP 125C, CSA FT6, CSA C(UL) TYPE CMP FT6, C(UL) TYPE CMP UL FT6; CSA FT6

Availability
Global
Status
Active
Orderable items
1

Ships from and sold by A5 IT.

Part numbers

58643 is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthOrder
58643 SL001SlateReel1,000 ftOrder online

Specifications

Product Overview

Suitable ApplicationsData, communication, audio, and low-level signal transmission; industrial networking, serial communication, control panels, automation equipment, and instrumentation systems.

Construction Details

Overall Cable Diameter (Nominal)0.309 in (7.85 mm)

Conductor

ElementPair(s)
No. of Elements3
Size16 AWG
Stranding7x25
MaterialTC - Tinned Copper

Insulation

ElementPair(s)
MaterialFEP - Fluorinated Ethylene Propylene
Nom. Thickness0.007 in (0.18 mm)
Nom. Insulation Diameter0.072 in (1.8 mm)
Color CodeBlack-Red, Black-White, Black-Green

Inner Shield

ElementPair(s)
Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type18 AWG (7x26.5) TC

Outer Jacket

MaterialPVDF - Polyvinylidene Fluoride
Nom. Thickness0.012 in (0.30 mm)
Nom. Diameter0.309 in (7.85 mm)

Electrical Characteristics

Electricals

ElementPair(s)
Nom. Capacitance Cond-to-Cond53 pF/ft (170 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)950 pF/ft (3100 pF/m)
Nom. Characteristic Impedence34 Ohm
Nom. Inductance0.14 μH/ft (0.46 μH/m)

Voltage

UL Voltage Rating300 V (CMP)

Mechanical Characteristics

Max. Pull Tension11 lbs (5.0 kg)

Temperature

UL Temperature125°C
Operating-25°C To +125°C

Bend Radius

Stationary Min.3.1 in (79 mm)

Standards and Compliance

Environmental SuitabilityIndoor
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 FT6 Loading, FT6
NEC / UL ComplianceArticle 800, CMP
CEC / C(UL) ComplianceCMP.
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlpha Wire -* P/N 58643 3PR 16 AWG SHIELDED 125C (UL) TYPE CMP OR C(UL) TYPE CMP FT6 CE ROHS

History