Belden Store
Belden5326FME

Product Number: 5326FME

Safe-T-Line, 8 C #18 Sol BC, Silicone Ins, OS, LSZH Jkt, FPLR, CWZ, PH120

Safe-T-Line 8 Conductor x AWG18 (Solid SBC) Fire resistant Multi-conductor, BS 6387 CWZ, EN 50200 PH120, EN60331-2 , Shielded, Ceramifiable Silicone insulation, Low Smoke Zero Halogen Jacket

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsFire Resistant Applications With Industrial Control, Raceways Cable trays and ducts, Digital Control, Instruments (4-20ma, 0-10v, ...),low voltage digital control (24v, ...), encoders, control circuits, distributed control system (DCS),programmable logic controller (PLC), Solenoids, Valves, Actuators, Positioners

Construction Details

Outer Jacket1 Table NotesHighly Flame Retardant Non-Halogenated Polyolefin

Conductor

ElementConductor(s)
No. of Elements8
Size18 AWG
StrandingSolid
MaterialBC - Bare Copper

Insulation

ElementConductor(s)
MaterialSilicone Rubber
Nom. Thickness0.034 in (0.86 mm)
Nom. Insulation Diameter0.109 in (2.77 mm)
Color CodeBlack #1, Black #2, Black #3, Black #4, Black #5, Black #6, Black #7, Black #8

Outer Shield

Shield TypeTape
MaterialBi-Laminate (Alum+Poly)
Coverage100%
Drainwire Type20 AWG (7x28) TC

Outer Jacket

MaterialPO - Polyolefin
Nom. Thickness0.045 in (1.1 mm)
Nom. Diameter0.457 in (11.6 mm)
RipcordYes

Electrical Characteristics

Electricals

Nom. Conductor DCR6.84 Ohm/1000ft (22.4 Ohm/km)
Max. Current9.8 Amps per Conductor at 30oC

Voltage

UL Voltage Rating300 V

Mechanical Characteristics

Max. Pull Tension169.4 lbs (76.84 kg)
Bulk Cable Weight119 lbs/1000ft (177 kg/km)

Temperature

UL Temperature105°C
Operating-20°C to +105°C

Bend Radius

Stationary Min.4.57 in (116 mm)
Installation Min.4.57 in (116 mm)
Flexing Min.4.57 in (116 mm)

Standards and Compliance

Environmental SuitabilityIndoor Riser, Indoor, Outdoor, Non-Halogenated, Sunlight Resistance
Flammability / Reaction to FireUL 1666 riser, 1202, IEC 60331-21, BS EN 50200 PH120
NEC / UL ComplianceArticle 760, FPLR, ITC, PLTC
European Directive ComplianceEU Directive 2011/65/EU (RoHS 2)
APAC ComplianceChina RoHS II (GB/T 26572-2011)
Other Standard Compliance(s)BS 6387 CWZ, EN50200 PH120
Plenum NumberNo

History

Update and RevisionRevision Number: 0.44 Revision Date: 07-21-2026

Resources

Related multi-conductor cable