Belden Store
Belden5072C

Product Number: 5072C

XTRAGUARD 1, 2C #16, Str, PVC, 300 V, AWM/STYLE 2464 80C, CM 105C, VW-1, AWM/STYLE 1569 105C, AWM/STYLE 2517 105C, SUN RES, CSA C(UL) TYPE CMG, CSA FT4

XTRAGUARD 1, 2 Conductor 16 AWG (19/.0117) TC - Tinned Copper, PVC Insulation, Slate PVC Outer Jacket, AWM/STYLE 2464 80C, CM 105C, VW-1, AWM/STYLE 1569 105C, AWM/STYLE 2517 105C, SUN RES, CSA C(UL) TYPE CMG, CSA FT4 C(UL) TYPE CMG, FT4 UL FT4, VW-1; CSA FT4; EN 60332-1 Flame Behavior; EN 60332-2 Flame Behavior

Availability
Global
Status
Active
Orderable items
2

Ships from and sold by A5 IT.

Part numbers

5072C is a product family. Each item number below is a separate orderable part — colour, put-up and length differ.

Item #ColorPutup TypeLengthOrder
5072C BK199BlackCut to Length1 ftOrder online
5072C SL005SlateReel100 ftOrder online

Specifications

Product Overview

Suitable ApplicationsIndustrial control systems, raceways, cable trays, and ducts; instrumentation and control circuits; analog and digital signals (4–20 mA, 0–10 V); PLC and DCS systems; sensors, encoders, solenoids, valves, actuators, and positioners.

Construction Details

Overall Cable Diameter (Nominal)0.250 in (6.35 mm)

Conductor

ElementConductor(s)
No. of Elements2
Size16 AWG
Stranding19x29
MaterialTC - Tinned Copper

Insulation

ElementConductor(s)
MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.016 in (0.41 mm)
Nom. Insulation Diameter0.091 in (2.3 mm)
Color CodeBlack, Red

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.032 in (0.81 mm)
Nom. Diameter0.250 in (6.35 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Capacitance Cond-to-Cond32 pF/ft (100 pF/m)
Nom. Characteristic Impedence63 Ohm
Nom. Inductance0.17 μH/ft (0.56 μH/m)

Voltage

UL Voltage Rating300 V (CMG, CM, AWM 2464, AWM 2517)

Mechanical Characteristics

Max. Pull Tension14.1 lbs (6.40 kg)

Temperature

UL Temperature105°C
Operating-30°C To +105°C

Bend Radius

Stationary Min.1.2 in (30 mm)
Installation Min.1.2 in (30 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 FT4 Loading, FT4, IEC 60332-1-2, IEC 60332-2-2
NEC / UL ComplianceArticle 800, CMG, CM
AWM ComplianceAWM 2464 AWM 2517
CEC / C(UL) ComplianceCMG.
European Directive ComplianceEU Directive 2015/863/EU (RoHS 2 amendment), REACH, EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE)
UK Regulation ComplianceUKCA Mark
APAC ComplianceChina RoHS II (GB/T 26572-2011)

Product Notes

NotesAlpha Wire -* P/N 5072C 2C 16 AWG XTRAGUARD(R) 1 (UL) TYPE CM 105C SUN RES OR AWM 2464 80C 300V OR AWM 2517 105C 300V VW-1 OR C(UL) TYPE CMG 105C FT4 CE ROHS OIL RESISTANT (SEQ FOOTAGE)

History

Update and RevisionRevision Number: 0.123 Revision Date: 06-30-2026

Resources

Related multi-conductor cable