Belden Store
1229503

Product Number: 1229503

VFD 300% Gnd, 3C+G #10 Str TC, XLPE Ins+PVC Gnd, OS+TC Brd w/#12 TC Drain, PVC Jkt, AIA Armor, Blk PVC Jkt, 600V MC 90C Dry/Wet

Belden 300% Ground Flexible VFD, 3 Conductor 10AWG (105x30) Tinned Copper, XLPE Insulation M4 Color Code+PVC Insulated Ground, Overall Beldfoil®+Tinned Copper Braid(85%) Shield w/12AWG Tinned Copper Drain, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, 600V MC 90C Dry/Wet SUN RES DIR BUR CT USE Oil Resistant

Availability
Global
Status
Active

Ships from and sold by A5 IT.

Specifications

Product Overview

Suitable ApplicationsVariable Frequency Drives (VFD); AC Motor and Drive Systems; Exposure to rodents, crush or impact forces

Construction Details

Overall Cable Diameter (Nominal)1.015 in (25.78 mm)

Conductor

ElementNo. of ElementsSizeStrandingMaterial
Conductor(s)310 AWG105x30TC - Tinned Copper
Ground110 AWG105x30TC - Tinned Copper

Insulation

ElementMaterialNom. ThicknessColor Code
Conductor(s)XLPE - Cross-Linked Polyethylene (Thermoset)0.046 in (1.2 mm)Black and Numbered
GroundPVC - Polyvinyl Chloride0.046 in (1.2 mm)Green/Yellow Stripe

Outer Shield

Shield TypeMaterialCoverage
TapeTri-Laminate (Alum+Poly+Alum)100%
BraidTinned Copper (TC)85%

Inner Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Diameter0.690 in (17.5 mm)

Armor

Armor Type & MaterialAIA - Aluminum Interlock Armor

Outer Jacket

MaterialPVC - Polyvinyl Chloride
Nom. Thickness0.050 in (1.3 mm)
Nom. Diameter1.015 in (25.78 mm)
RipcordYes

Electrical Characteristics

Electricals

ElementConductor(s)
Nom. Conductor DCR0.968 Ohm/1000ft (3.18 Ohm/km)
Nom. Capacitance Cond-to-Cond44 pF/ft (140 pF/m)
Nom. Capacitance Cond-to-Other (Conds + Shield)79 pF/ft (260 pF/m)
Nom. Characteristic Impedence53 Ohm
Nom. Velocity of Prop.55%
Max. Current24 Amps per Conductor at 30oC

Voltage

UL Voltage Rating600 V (MC)

Mechanical Characteristics

Max. Pull Tension603 lbs (274 kg)
Bulk Cable Weight547 lbs/1000ft (814 kg/km)

Temperature

UL Temperature90°C Dry, 90°C Wet
Operating-25°C To +90°C

Bend Radius

Stationary Min.12.2 in (310 mm)
Installation Min.12.2 in (310 mm)

Standards and Compliance

Environmental SuitabilityIndoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial
SustainabilityCA Prop 65
Flammability / Reaction to FireUL1685 FT4 Loading
NEC / UL ComplianceArticle 336, MC
APAC ComplianceChina RoHS II (GB/T 26572-2011)

History

Update and RevisionRevision Number: 0.59 Revision Date: 04-06-2026

Resources

Related armored teck & mc cable