Belden Cable
Call for Price
Ships from and sold by A5 IT
Call for pricing
This part is quoted to order. Call for current pricing, lead time and volume breaks on the Belden 29726C 0105000.
224-955-1644Free 2-3 Day Shipping within the United StatesShips as soon as stock arrives. We'll confirm the lead time before your card is charged.
New, with full manufacturer warranty
Key Features
- Suitable Applications: Variable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements
- Outer Jacket Material: PVC - Polyvinyl Chloride
- Outer Jacket Nom. Thickness: 0.083 in (2.1 mm)
- Outer Jacket Nom. Diameter: 0.973 in (24.7 mm)
- Outer Jacket Ripcord: Yes
- Electricals Element: Conductor(s)
- Electricals Nom. Conductor DCR: 0.223 Ohm/1000ft (0.732 Ohm/km)
- Electricals Nom. Capacitance Cond-to-Cond: 40 pF/ft (130 pF/m)
Belden 29726C 0105000 is an orderable item number in the Belden 29726C family (Cable › VFD Cable). Belden Basics VFD, 3 Conductor 4AWG (7x12) Bare Copper XLPE Insulation M4 Color Code + 6AWG Symmetrical Segmented Ground (3 of 12AWG) Bare Copper Stranded, Overall Dual Copper Tapes Helically Applied Shield, Black PVC Outer Jacket, 2000V TC-ER 90C Dry/Wet 1000V CSA AWM I/II A/B SUN RES DIR BUR Oil Resistant This item: Putup Type Reel, UPC 612825445692. Ships from and sold by A5 IT. Quoted to order.
History
| Update And Revision | Revision Number: 0.86 Revision Date: 04-01-2026 |
This Item
| UPC | 612825445692 |
| Putup Type | Reel |
| Item Number | 29726C 0105000 |
Information
| Put-Up Type | Reel |
| Update And Revision | Revision Number: 0.86 Revision Date: 04-01-2026 |
Product Overview
| Suitable Applications | Variable Frequency Drives (VFD); AC Motor and Drive Systems; High voltage requirements |
Construction Details
| Conductor Row 1 — Size | 4 AWG |
| Conductor Row 2 — Size | 12 AWG |
| Outer Jacket — Ripcord | Yes |
| Conductor Row 1 — Notes | ASTM B3 Copper B8 Class B Stranding |
| Conductor Row 2 — Notes | Segmented Grounds |
| Outer Jacket — Material | PVC - Polyvinyl Chloride |
| Conductor Row 1 — Element | Conductor(s) |
| Conductor Row 2 — Element | Ground |
| Conductor Row 1 — Material | BC - Bare Copper |
| Conductor Row 2 — Material | BC - Bare Copper |
| Insulation Row 1 — Element | Conductor(s) |
| Insulation Row 2 — Element | Ground |
| Conductor Row 1 — Stranding | 7x12 |
| Conductor Row 2 — Stranding | 7x20 |
| Insulation Row 1 — Material | XLPE - Cross-Linked Polyethylene (Thermoset) |
| Insulation Row 2 — Material | No Insulation |
| Outer Jacket — Nom. Diameter | 0.973 in (24.7 mm) |
| Insulation Row 1 — Color Code | Black and Numbered |
| Outer Jacket — Nom. Thickness | 0.083 in (2.1 mm) |
| Outer Shield Row 1 — Coverage | 100% |
| Outer Shield Row 1 — Material | Bare Copper (BC) |
| Outer Shield Row 2 — Coverage | 100% |
| Outer Shield Row 2 — Material | Bare Copper (BC) |
| Overall Cable Diameter (Nominal) | 0.973 in (24.7 mm) |
| Outer Shield Row 1 — Shield Type | Helical Tape |
| Outer Shield Row 2 — Shield Type | Helical Tape |
| Conductor Row 1 — No. Of Elements | 3 |
| Conductor Row 2 — No. Of Elements | 3 |
| Insulation Row 1 — Nom. Thickness | 0.072 in (1.8 mm) |
| Insulation Row 1 — Nom. Insulation Diameter | 0.369 in (9.37 mm) |
Standards And Compliance
| AWM Compliance | I/II A/B |
| Sustainability | CA Prop 65 |
| APAC Compliance | China RoHS II (GB/T 26572-2011) |
| ICEA Compliance | S-95-658 |
| NEC / UL Compliance | Article 336, TC-ER, RHW-2 |
| Environmental Suitability | Indoor, Outdoor, Sunlight Resistance, Oil Resistance, Burial |
| Other Standard Compliance(s) | P-07-KA070003-MSHA |
| European Directive Compliance | EU CE Mark, EU Directive 2015/863/EU (RoHS 2 amendment), EU Directive 2011/65/EU (RoHS 2), EU Directive 2012/19/EU (WEEE) |
| Flammability / Reaction To Fire | UL1685 UL Loading, 1202, 383 Vertical Tray Flame Test (70,000 BTU) |
Electrical Characteristics
| Electricals — Element | Conductor(s) |
| Electricals — Max. Current | 95 Amps per Conductor at 30oC |
| Voltage — UL Voltage Rating | 2000 V (TC), 1000 V (CSA AWM I/II A/B) |
| Electricals — Nom. Conductor DCR | 0.223 Ohm/1000ft (0.732 Ohm/km) |
| Electricals — Nom. Velocity Of Prop. | 55% |
| Electricals — Nom. Capacitance Cond-to-Cond | 40 pF/ft (130 pF/m) |
| Electricals — Nom. Characteristic Impedence | 46 Ohm |
| Electricals — Nom. Capacitance Cond-to-Other (Conds + Shield) | 72 pF/ft (240 pF/m) |
Mechanical Characteristics
| Bulk Cable Weight | 738 lbs/1000ft (1100 kg/km) |
| Max. Pull Tension | 1919 lbs (870.4 kg) |
| Temperature — Operating | -40°C To +90°C |
| Temperature — UL Temperature | 90°C Dry, 90°C Wet |
| Bend Radius — Stationary Min. | 11.7 in (297 mm) |
| Bend Radius — Installation Min. | 11.7 in (297 mm) |
Purchasing this for your business?